Provides detection for various A2L and A3 gases (R32, R454A, R454B, R454C, R290)
0-100% LFL refrigerant gas measurement range
High accuracy across full temperature and humidity range
Advanced automatic baseline calibration mechanism, no field calibration required
Integrated mitigation/shutdown functions
Fast response speed, service life up to 15 years
Principle: NDIR
Measured gases: R32 / R454A / R454B / R454C / R290
Measurement range: 0–100% LFL
Accuracy: ±2.5% LFL @ 0%–25% LFL
±10% of reading @ 25%–100% LFL
Resolution: 0.1% LFL
Response time: T90 ≤ 30 s
Output: RS485 Modbus; Relay output
Protection rating: IP54
Operating conditions: -30 ~ 70 °C, 0–95% RH (non-condensing)
Storage conditions: -40 ~ 85 °C, 0–95% RH (non-condensing)
Power supply: AC: 18~36 V, standard 24 V, 55 ± 8 Hz
DC: 12~36 V, standard 24 V
Service life: >15 years
Dimensions: 103.2 × 80 × 30.5 mm (customizable)